Product Origin:
ChinaItem NO.:
Diesel Generator Control Module DSE5110
Power Supply |
8 to 35 Vdc Continuous |
Cranking Dropouts: |
Able to survive 0 V for 50 mS, providing supply was at least 10 V |
Max Current |
Operating 425mA at 12 V & 215mA at 24 V; Standby 250 mA at 12 V & 125 mA at 24 V. |
Start Relay Output: |
16 Amp DC at supply voltage. |
Fuel Relay Output: |
16 Amp DC at supply voltage. |
Auxiliary Relay Outputs: |
5 Amp DC at supply voltage. |
Charge Fail / ExcitationRange |
0 V to 35 V |
Maximum operating current |
320ma at 12V, 215ma at 24v |
Maximum operating current |
175ma at 12V, 95ma at 24v |
AlternatorInputRange: |
15V(L-N) to 333V AC (L- N) absolute maximum |
Alternator Input Frequency: |
50 - 60 Hz at rated engine speed (Minimum: 15V AC Ph-N) |
Magnetic Pick-upVoltageInputRange: |
+/- 0.5 V to 70 V Peak |
Magnetic Input Frequency: |
10,000 Hz (max) at rated engine speed |
MAINS (UTILITY) SENSING INPUT RANGE |
(DSE5220 only) |
MAINS(UTILITY)SENSINGINPUTFREQUENCY |
(DSE5220 only) |
MAINS (UTILITY) & GENERATOR LOADING |
(DSE5220 only) |
Generator loading Relay Output: |
8 Amp AC 250V. |
Mains loading Relay Output: |
8 Amp AC 250V |
Panel Cutout: |
220mm x 160mm ( 8.7" x 6.3") |