Product Origin:
ChinaItem NO.:
Diesel Engine Electronic Control Module DSE705 With ATS FunctionMain Features:
Protected solid state (PSS) outputs
Front panel mounting
Front panel programming
LED indicators
Configurable timers
Configurable outputs
Single/three phase mains sensing
Benefits:
Transfer�s between mains and generator power
On-site module configuration to match user requirements
Operation:
The module is operated by the three push-buttons on the front:
Manual Off Load �This is used to manually start and run the engine off load. Should the mains (utility) supply fail, then the load is transferred to the generator automatically.
Manual On Load - This mode is used to manually start and run the engine on load.
Auto Mode �This puts the module into automatic mode, where it will await a mains failure. Upon detection it will send a start request to the generator control unit.
DC SUPPLY |
Continuous Voltage Rating |
8 V to 35 V continuous |
Maximum Operating Current |
100 mA at 12 V, 105 mA at 24 V |
|
Maximum Standby Current |
60 mA at 12 V, 55 mA at 24 V |
|
Maximum Sleep Current |
40 mA at 12 V, 35 mA at 24 V |
|
Cranking Droputs |
Able to survive 0 V for 50 mS, providing supply was at least |
|
10 V before dropout and supply recovers to 5 V |
||
This is achieved without the need for internal batteries |
||
INPUTS |
Digital Inputs A to F |
Negative switching |
Analogue Inputs D |
Configurable as: |
|
Negative switching digital input |
||
0 V to 10 V,4 mA to 20 mA,0 ? to 240 ? |
||
Analogue Inputs A TO C |
Configurable as: |
|
|
Negative switching digital input:0 ? to 480 ? |
|
OUTPUTS |
Output A (Fuel) |
10 A short term, 5 A continuous,at supply voltage |
Output B (Start) |
10 A short term, 5 A continuous,at supply voltage |
|
Auxiliary Outputs C, D, E &F |
2 A DC at supply voltage |
|
GENERATOR & MAINS (UTILITY) |
Voltage Range |
15 V to 415 V AC (Ph to N),26 V to 719 V AC (Ph to Ph) |
Frequency Range |
3.5 Hz to 75 Hz |